HORIZONTAL DISCHARGE SPLIT SYSTEM AIR CONDITIONING-1THRU 2TON


DESCRIPTION/APPLICATION

PHYSICAL DATA
ELECTRICAL DATA
NOMINAL PERFORMANCE RATING

 

 

DESCRIPTION/APPLICATION :

  Model Series HDCF Are For Split System Air Conditioning Applications

  Modern Compact Design With Quiet Operating Horizontal Discharge Air

  Narrow Footprint Ideal For Ground Level, Rooftop, Or Wall Mounting

  Designed For Use With Typical Mini Split Indoor Section As Well As, Standard Air Handlers Or Indoor Coils

CABINET CONSTRUCTION :

  Steel Sheet Metal Shall Be Durable Baked Enamel Finish

STANDARD EQUIPMENT :

  Copper Tube, Aluminum Fin Construction

  Brass Suction And Liquid Line Shut Off Valves With Flare Connections

  Liquid Shut Off-Valve Provided With Built In Flow Rater Expansion Device

  Fully Charged For 15' Tubing Length

  Line Voltage Control Circuit Suitable For Connection To Typical Mini Split Indoor Section

  Totally Enclosed Permanently Lubricated Condenser Motor

  Isolated Compressor Compartment

  Liquid Line Filter Drier Factory Installed

  Quiet Hermetically Sealed Reciprocating Compressor With Internal Overload Protection Or Rotary Compressor With External Overload Protection

PHYSICAL DATA

ITEM HDECF12-2 HDECF18-2 HDECF24-2
FAN
DIA. CM(IN) 6.3 (16) 7.1 (18) 7.1 (18)
RPM 950 950 950
COIL
FACE AREA M² (FT²) 0.58 (5.2) 0.73 (6.5) 0.73 (6.5)
TUBE DIA. MM (IN) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
NO. ROWS / FINS CM (IN) 1 / 7.5 (19) 1 / 7.5 (19) 1 / 7.5 (19)
NO. OF TUBES 16 20 20
FIN TYPE RIPPLED RIPPLED RIPPLED
REFRIGERANT CON.
LIQUID DIA. MM (IN) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
SUCTION DIA. MM (IN) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
TYPE FLARE FLARE FLARE
WEIGHT KG (LBS) 52 (115) 56 (125) 65 (130)

DIMENSIONAL DATA

ELECTRICAL DATA

Model Power Supply **Minimum
Circuit
Ampacity
*Maximum
Over Current
Protection
Maximum
Volts
Minimum Volts Compressor Cond. Fan
Volts PH HZ FLA LRA Volts FLA LRA Volts
HDCF12-2 220/240 1 50 11.2 15 264 197

7.5

43

240/1/50

0.5 1/15 208-230
HDCF18-2 220/240 1 50 15.2 25 264 197

10.6

52

240/1/50

0.5 1/15 208-230
HDCF24-2 220/240 1 50 18.9 30 264 197

13.3

72

240/1/50

0.5 1/15 208-230

* MAY USE FUSES OR HACR TYPE CIRCUIT BREAKERS OF THE SAME SIZE AS NOTED
** FOR SELECTION WIRE SIZE

WIRING DIAGRAM
LINE VOLTAGE CONTROL CIRCUIT
(TYPICAL WIRING FOR USE WITH
DUCTLESS INDOOR SECTION)
WIRING DIAGRAM
LOW VOLTAGE CONTROL CIRCUIT
(TYPICAL WIRING FOR USE WITH
DUCTED INDOOR SECTION)

NOMINAL PERFORMANCE RATING

Model 95°F OD 80/67°F ID KCALH
BTUH
115°F OD 80/67°F ID KCALH
BTUH
Outdoor Indoor Total Sensible KW Total Sensible KW
HDCF12-2 WMC12-2 3025
(12000)
2326
(9230)
1.5 2671
(10600)
2056
(8150)
1.75
HDCF12-2 A18-00-2 2772
(11000)
1990
(7900)
1.22 2872
(11400)
1738
(6900)
1.44
HDCF18-2 WMC18-2 4387
(17400)
3377
(13400)
2.1 3628
(14400)
3402
(12500)
3.4
HDCF18-2 A18-00-2 4435
(17600)
3276
(13000)
1.95 3855
(15300)
3061
(12150)
2.20
HDCF18-2 A24-00-2 4536
(18000)
3453
(13700)
1.89 3981
(15800)
3024
(12000)
2.50
HDCF24-2 WMC12-2 5496
(21800)
4213
(16720)
3.1 4737
(18800)
3900
(15500)
3.4
HDCF24-2 A24-00-2 5796
(23000)
4284
(17000)
2.87 5040
(20000)
4007
(15900)
3.12

- ERR = ENERGY EFFICIENCY RATIO = CAPACITY (BOTH) KW INPUT
- KWI = COMPRESSOR + INDOOR BLOWER + OUTDOOR FAN WATTS
- OD = OUTDOOR DRY BULB TEMPERATURE - DEGREE F
- ID = INDOOR DRY BULB/WET BULB TEMPERATURE - DEGREE F

NOTE:
SPECIFICATIONS AND PERFORMANCE DATA LISTED HERE IN ARE SUBJECT TO CHANGE WITHOUT NOTICE.