DESCRIPTION/APPLICATION :
Compact
Versatile Uoflow, Or Horizontal Multi-Position. May Be Located
In Closet, Utility Room, Attic, Crawl Space, Or Basement
CONSTRUCTION :
Insulated
Steel Cabinet
CABINET FINISH :
Durable
Baked Enamel Finish
STANDARD EQUIPMENT :
Fully
Insulated Cabinet
Direct
Drive Multi-Speed Motor To Permit Air Volume Variation
For The Heating And Cooling Application Needs
Equipped
With A Check Flow Rater For Heat Pump And Cooling Unit
Operation
Built In
Coil With Horizontal And Vertical Drain Pans With
Secondary Drains
Power
Supply Entry At Top
Low
Voltage Entry On Left Side And Tested
Built-In
Filter Provisions (See Filter Chart)
A24-00-2
/A36-00-2
INLET
FRONT VIEW |
 |
|
A24-00-2
/A36-00-2
INLET
RIGHT SIDE VIEW |
 |
|
|
|
|
FILTER-PERMANENT WASHABLE
|
|
|
MODEL |
A |
B |
C |
D |
|
A24-00-2 |
106 |
40 |
35 |
35 |
|
A36-00-2 |
118 |
50 |
45 |
45 |
|
|
MODEL |
FILTER
SIZE
(Actual Dimensions) |
|
A24-00-2 |
37 x 55 x 1.8 |
|
A36-00-2 |
47 x 55 x 1.8 |
|
A48-00-2 |
53 x 60 x 1.8 |
|
A60-00-2 |
53 x 60 x 1.8 |
|
A48-00-2
/A60-00-2
INLET
FRONT VIEW |
 |
|
A48-00-2
/A60-00-2
INLET
RIGHT SIDE VIEW |
 |
|
|
|
|
Model
No. |
Blower |
Coil
Drain Conn. FPT |
Refrigerant
Connections |
Net
Weight KG |
|
Dia. In. |
Width
In. |
Lip. |
Suct. |
|
A24-00-2 |
9 |
8 |
3/4 |
3/8 |
3/4 |
47 |
|
A36-00-2 |
10 3/4 |
7 7/8 |
3/4 |
3/8 |
3/4 |
63 |
|
A48-00-2 |
10 3/4 |
10 5/8 |
3/4 |
3/8 |
7/8 |
73 |
|
A60-00-2 |
10 3/4 |
10 5/8 |
3/4 |
3/8 |
7/8 |
74 |
|
|
|
|
Model
No. |
Maximum
Over Current
Port. Amps
@208/230V |
Minimum
VAC |
Maximum
VAC |
Blower
Motro |
|
FLA |
HP |
|
A24-00-2 |
15 |
198 |
264 |
0.8 |
1/4 |
|
A36-00-2 |
15 |
198 |
264 |
1.5 |
1/2 |
|
A48-00-2 |
15 |
198 |
264 |
2.1 |
3/4 |
|
A60-00-2 |
15 |
198 |
264 |
2.1 |
3/4 |
|
|
SCHEMATIC WIRING DIAGRAM
"A" SERIES
A24-00-2, A36-00-2, A48-00-2, A60-00-2
ELECTRIC AIR HANDLER |
|
 |
|
|
|
MODEL |
MOTOR
SPEED |
CFM
Delivered Agonist
External Static Pressure H20 |
|
|
0.1 |
0.2 |
0.3 |
0.4 |
0.5 |
|
A24-00-2 |
High |
1050 |
1000 |
950 |
900 |
850 |
|
Low |
900 |
850 |
800 |
750 |
700 |
|
A36-00-2 |
High |
1850 |
1800 |
1740 |
1640 |
1550 |
|
Low |
1665 |
1630 |
1580 |
1500 |
1390 |
|
A48-00-2 |
High |
2085 |
2000 |
1870 |
1800 |
1710 |
|
Low |
1675 |
1655 |
1635 |
1615 |
1600 |
|
A60-00-2 |
High |
2120 |
2040 |
1960 |
1870 |
1800 |
|
Low |
1800 |
1770 |
1745 |
1720 |
1700 |
|
|
- DRY COIL WITH