HYDRAULIC AIR HANDLER FOR HEATING AND AIR CONDITIONING


DESCRIPTION/APPLICATION
PHYSICAL DATA
ELECTRICAL DATA
BLOWER PERFORMANCE
 
 

DESCRIPTION/APPLICATION :

  Compact, Versatile Up Flow, Or Horizontal Multi-Position. May Be Located In Closet, Utility Room, Attic, Crawl Space, Or Basement

CONSTRUCTION :

  Insulated Steel Cabinet

CABINET FINISH :

  Durable Backed Enamel Finish

STANDARD EQUIPMENT :

  Fully Insulated Cabinet

  Direct Drive Multi-Speed Motor To Permit Air Volume Variation For The Heating And Cooling Application Needs

  Equipped With a Check Flow Rater For Heat Pump And Cooling Unit Operation

  Built In Coil With Horizontal And Vertical Drain Pans With Secondary Drains

  Power Supply Entry At Top

  Low Voltage Entry On Left Side And Top

  Factory Installed, Wired, And Tested

  Built-In Filter Provisions (See Filter Chart)

  Equipped With Hot Water Coil, Constructed Of Copper Tube And Aluminum Finn

  Performance Ratings

H.P.A24-00-2 /A36-00-2
INLET
FRONT VIEW
H.P.A24-00-2 /A36-00-2
INLET
RIGHT SIDE VIEW

MODELS

FILTER-PERMANENT WASHABLE 

MODEL A B C D
H.P.A24-00-2 123 40 35 34
H.P.A36-00-2 134 50 45 44
MODEL FILTER SIZE
(Actual Dimensions)
H.P.A24-00-2 37 x 55 x 1.8
H.P.A36-00-2 47 x 55 x 1.8
H.P.A48-00-2 53 x 60 x 1.8
H.P.A60-00-2 53 x 60 x 1.8
MODEL COMPANY
COOLING
NOMINAL
BTUH / H
CAPACITY
HEATING
L.W.T
140°F
H.P.A24-00-2 24000 48000
H.P.A36-00-2 36000 70000
H.P.A48-00-2 48000 120000
H.P.A60-00-2 66000 120000
H.P.A48-00-2 /A60-00-2
INLET
FRONT VIEW
H.P.A48-00-2 /A60-00-2
INLET
RIGHT SIDE VIEW

PHYSICAL DATA

Model No. Blower Coil Drain Conn. FPT Refrigerant
Connections
Net Weight KG
Dia. In. Width In. Lip. Suct.
H.P.A24-00-2 9 8 3/4 3/8 3/4 60
H.P.A36-00-2 10 3/4 7 7/8 3/4 3/8 3/4 81
H.P.A48-00-2 10 3/4 10 5/8 3/4 3/8 7/8 100
H.P.A60-00-2 10 3/4 10 5/8 3/4 3/8 7/8 102

ELECTRICAL DATA

Model No. Minimum
Ampacity
@208/230V
Maximum
Over Current
Port. Amps
@208/230V
Minimum
VAC
Maximum
VAC
Blower Motro
FLA HP
H.P.A24-00-2 1.06 15 198 264 0.8 1/4
H.P.A36-00-2 1.75 15 198 264 1.5 1/2
H.P.A48-00-2 3.18 15 198 264 2.1 3/4
H.P.A60-00-2 3.18 15 198 264 2.1 3/4

SCHEMATIC WIRING DIAGRAM "A" SERIES
H.P.A24-00-2, H.P.A36-00-2
H.P.A48-00-2, H.P.A60-00-2
ELECTRIC AIR HANDLER

BLOWER PERFORMANCE

MODEL MOTOR
SPEED
CFM Delivered Agonist
External Static Pressure H20
  0.1 0.2 0.3 0.4 0.5
H.P.A24-00-2 High 1050 1000 950 900 850
Low 900 850 800 750 700
H.P.A36-00-2 High 1850 1800 1740 1640 1550
Low 1665 1630 1580 1500 1390
H.P.A48-00-2 High 2085 2000 1870 1800 1710
Low 1675 1655 1635 1615 1600
H.P.A60-00-2 High 2120 2040 1960 1870 1800
Low 1800 1770 1745 1720 1700
H.P.A60-00-2 i High 2500 2400 2300 2230 2170
Low 2250 2200 2140 2100 2050

- DRY COIL WITH FILTER IN PLACE SCFM CORRECTION FOR WET COIL - 4%

Home | Profile | Resume | Products | Services | Contact Us

 

Copyright © 2003 Bernoulli Air Conditioning Co. All rights reserved. Designed by AryaWeb